Vitodens Fault Codes and 100 overview
Vitodens Fault Codes and 100 overview
Fault Code 10
Boiler mode: Vitodens 200-W / 222-F / Vitotronic 300 / 200/ 200-H / 050/200-H / 300-K / vitocontrol-S
System behaviour: Boiler operates based on outdoor temperature of 32°F / 0°C
Diagnosis: Short circuit – Outdoor temperature sensor
Fault Code F6, 58, F9, F-E1, F-E2 and F-F6
Boiler mode: All Viessmann boilers
System behaviour: Burner in fault mode / Emergency operation
Diagnosis: Fan not at standstill / plug-in connection
Fault Code D4
Boiler mode: Vitotronic 300 / Vitotronic 300-K with Vitotronic 300
System behaviour: Boiler cools down
Diagnosis: Fault, safety equipment at ” X2 / X3 / X7″ of plug-in adaptor 2 for external safety equipmentFan not at standstill / plug-in connection
—-
Boiler mode: Vitodens 200
System behaviour: Boiler operates in emergency mode (after approx. 30 min. BUS fault) OR Boiler cools down
Diagnosis: Internal BUS fault OR Open circuit – Internal BUS connection
Fault Code 18 and D1
Boiler mode: Vitodens 100 / 200-W / 222-F / Vitotronic 300-K With 100 / Vitocontrol-S
System behaviour: Boiler operates based on outdoor temperature of 32°F / 0°C / Constant Mode
Diagnosis: Outdoor temperature sensor cable broken
—-
Boiler mode: Vitotronic / 100 / 200 / 300 / 050/200-H /300-K / Vitocontrol-S, MW1 with Vitotronic 100
System behaviour: Operates on basis of 32°F / 0°C outdoor temperature
Diagnosis: Open circuit – Outdoor temperature sensor
—-
Boiler mode: Vitotronic 200-H / Vitotronic 300-K, MW1B with Vitotronic 300 / Vitotronic 300-K, MW2B with Vitotronic 200
System behaviour: Controls as if the outdoor temperature
Diagnosis: Lead break, Outdoor temperature sensor
—-
Boiler mode: Vitotronic 050/200-H
System behaviour: Activates after 0°C / 32°F outdoor temperature
Diagnosis: Cable break – Outdoor temperature sensor
—-
Boiler mode: Vitodens 100-W
System behaviour: Burner in fault mode
Diagnosis: DIP switch S2 is set to “ON”
Fault Code A4
Boiler mode: Vitodens 222F
System behaviour: Burner blocked. The venting program is started automatically
Diagnosis: Air lock in the Internal circulation pump or minimum flow rate not achieved
Fault Code OC
Boiler mode: Vitodens 100-W
System behaviour: Burner blocked
Diagnosis: Insufficient power supply
—-
Boiler mode: Vitodens 200
System behaviour: Burner control switches to lockout
Diagnosis: Flame signal still present after switching off